Chemstar WATER
  • Home
  • About Us
    • NEWS & INSIGHTS
    • CAREERS
    • OUR SAFETY COMMITMENT
    • SUPERIOR SERVICE
  • Solutions
    • COOLING WATER
    • MICROBIOLOGICAL CONTROL
    • LEGIONELLA PREVENTION
    • BOILER WATER
    • CLOSED LOOP
    • WATER & ENERGY SAVINGS
    • INFLUENT WATER
    • WASTE WATER
    • PRODUCTS
      • CHEMICALS
      • XCA® Monochloramine Generator
      • Vapor Phase Corrosion Inhibitor (VPCI)
      • ReImagined Glycol™
      • Sidestream Filtration
    • SERVICES
      • Water Management Plan (WMP)
      • Emergency Mobile Disinfection Skid
      • Water Testing Lab Services
      • ST108 Compliance
      • Cooling Tower Cleaning
      • Commercial Ice Machine Cleaning
      • Deionized (DI) Portable Tank Exchange
  • INDUSTRIES
    • DATA CENTERS
    • HEALTHCARE
    • FOOD & BEVERAGE
    • INDUSTRIAL
    • NEW CONSTRUCTION
    • GOVERNMENT & INSTITUTIONS
    • COMMERCIAL
    • PROPERTY MANAGEMENT
  • Case Studies
    • WATER SAFETY HOSPITAL EXPANSION
    • HYPERSCALE DATA CENTER
    • REMOVING BIOFILM AT MEDICAL CENTER
    • INDUSTRIAL BAKERY
    • CENTRAL UTILITY PLANT
  • Contact Us
  • Click to open the search input field Click to open the search input field Search
  • Menu Menu
  • Link to LinkedIn

7 Hidden Dead Legs in Cooling Towers: A Powerful Guide to Eliminating Stagnant Risks

Table of Contents

  • 1. Why Dead Legs in Cooling Towers Demand Urgent Attention
  • 2. Dead Leg #1 – Kept Piping Extensions for Future Expansion
  • 3. Dead Leg #2 – (Balance) Equalization Lines
  • 4. Dead Leg #3 – Standby Recirculation Pump Headers
  • 5. Dead Leg #4 – Standby Chiller & Idle Condenser Water Loops
  • 6. Dead Leg #5 – Free-Cooling Heat-Exchanger (Economizer) Circuits
  • 7. Dead Leg #6 – Piping Drop Legs & Blind Stubs
  • 8. Dead Leg #7 – Out-of-Service Sand Filters
  • 9. Proven Operations & Maintenance (O&M) Tactics
  • 10. Design Upgrades to Make Dead Legs Disappear
  • 11. The Bottom Line for Facility Managers

1. Why Dead Legs in Cooling Towers Demand Urgent Attention

Dead legs in cooling towers are stagnant sections of piping, vessels, or equipment where water circulation is insufficient or non-existent. They create ideal breeding grounds for biofilm, Legionella, sulfate-reducing bacteria, under-deposit corrosion, and scale formation.

For mission-critical facilities—data centers, hospitals, food plants—one undetected dead leg can escalate into performance loss, compliance violations, or even a shutdown.

What’s in it for me? Eliminating dead legs improves microbial control, stabilizes water chemistry, reduces unplanned downtime, and drives cost-effective, sustainable operation.

Regulatory bodies such as ASHRAE 188, CDC, and OSHA highlight stagnant sections as high-risk zones. Yet many facilities unknowingly host multiple hidden dead legs because their systems evolved over time—extensions left for future expansion, spare pumps on standby, or economizer loops that only run seasonally.

2. Dead Leg #1 – Kept Piping Extensions for Future Expansion

What it is: A capped branch or long spool installed for potential plant expansion. Until that day arrives, the water trapped inside stagnates.

Operational risk: Rapid bacterial growth within 48 hours; scale plates out as temperature fluctuates, seeding the main loop once flow resumes.

  • Install a drain line or cross-connection back to the supply header so water can flush naturally.
  • Automate flushing with a timer or PLC—5 minutes at least twice a week during regular biocide additions.
  • Document expansion stubs in P&IDs and preventive-maintenance schedules so they aren’t forgotten.
Large yellow and orange industrial pipes with bolted ends run horizontally in front of cooling towers and machinery on a rooftop facility under a cloudy sky.

Piping extensions with bolted ends run horizontally in front of cooling towers and machinery on a rooftop facility under a cloudy sky.

3. Dead Leg #2 – Equalization Lines

Also called “balance”, equalizer or equalization lines, these side connections equalize water levels between basins. If valved off or hydraulically throttled, they turn into stagnant zones.

  • Keep the valve cracked open to maintain a minimum scouring velocity of 3 ft s⁻¹.
  • Add an automatic flushing valve on a 72-hour timer when equalization flow is normally zero.
  • Install a flush-through bypass for thorough rinsing during tower offline periods (>5 days).
Large industrial air conditioning unit with metal grilles, pipes, and valves installed on a building rooftop. The unit is supported by a metal frame and surrounded by urban structures.

Large industrial air conditioning unit with metal grilles, pipes, and valves installed on a building rooftop with a visible equalization line. 


4. Dead Leg #3 – Standby Recirculation Pump Headers

Facilities commonly keep a standby pump in the cooling-tower loop. The suction and discharge headers beyond the closed isolation valves become stagnant.

  • Exercise the pump 2–3 times a week for 15 minutes—ideally coinciding with biocide feed.
  • If cycling isn’t possible, cross-tie the standby header with a small balance line to the active header for continuous low-flow flushing.
  • Thermally trend the standby casing; a temperature rise can indicate microbiological fouling.
A row of industrial pumps with red valves and insulated pipes at an outdoor facility, surrounded by metal frames and a blue heat exchanger under a clear sky.

A row of industrial recirculation pumps with red valves, steel headers and insulated pipes for a rooftop cooling tower installation, surrounded by metal frames and a blue heat exchanger under a clear sky.

5. Dead Leg #4 – Standby Chiller & Idle Condenser Water Loops

Redundant chillers safeguard uptime, but their isolated condenser bundles, vent lines, and bypasses transform into dead legs in cooling towers when out of service for extended periods.

  • Establish flow through all idle chiller bundles 2–3 times a week—particularly during oxidizing biocide additions.
  • If idle for >5 days, perform a flush-and-disinfect protocol before returning to duty.
  • Consider a “mini-flow” recirculation line sized at 5 % of design flow to keep water moving.

Large industrial pipes, mostly orange and silver, run through a mechanical room. Blue valves and control units are attached to the pipes, along with various fittings and support beams, creating a complex network.

Chiller and condenser water loops, in red and steel with visible valves in a mechanical room.


6. Dead Leg #5 – Free-Cooling Heat-Exchanger (Economizer) Circuits

Economizers are seasonal; their plate or shell-and-tube exchangers can sit idle from late spring through early fall. Internal channels become classic dead legs.

  • Schedule bi-weekly mini-operations (open bypass valve, run bypass pump, throttle tower fans) to flush the exchanger.
  • Drain and dry-layup exchangers projected to stay idle >30 days—then disinfect on refill.
  • Add removable spool pieces for mechanical cleaning and video inspection every season.
Two large industrial cooling fans with protective metal grates and surrounded by orange pipes are installed on a rooftop within a rectangular concrete enclosure.

Two large industrial cooling fans with protective metal grates and surrounded by orange pipes are installed on a rooftop within a rectangular concrete enclosure.

7. Dead Leg #6 – Piping Drop Legs & Blind Stubs

Vertical drop legs—especially those feeding chemical sensors, blowdown lines, or side-stream devices—invite debris settling. Blind stubs left after rerouting can pool stagnant water.

  • Re-route instruments to the main header elevation when feasible.
  • Remove abandoned stubs or saw-cut and cap at the header to eliminate the dead volume.
  • Where removal isn’t practical, install a continuous bleed or timed flush to scour the drop leg.

A row of industrial pipes and valves, with four large red valve handles and blue motorized pumps below, mounted against a concrete wall in a mechanical or utility room.

A row of industrial pipes and valves of a cooling tower, with four large red valve handles and blue motorized pumps below, mounted against a concrete wall in a mechanical or utility room.


8. Dead Leg #7 – Out-of-Service Sand Filters

Side-stream sand filters controlled by differential pressure often remain offline for weeks. The filter vessel and multi-valve header become bacterial incubators.

  • If out of service >5 days, replace sand media and disinfect the housing and piping before restarting.
  • Integrate an automatic bypass flush every 48 hours to refresh water and prevent stagnation.
  • Upgrade to self-indexing media filters or disposable cartridge skids that operate continuously at low flow.

9. Proven Operations & Maintenance (O&M) Tactics

  • Synchronize flushing with biocide feed: Maximum kill occurs when fresh oxidant contacts the flushed dead leg.
  • Maintain a dead leg inventory log: Track length, diameter, location, flushing frequency, and last inspection date.
  • Use vertical integration advantages: Water-treatment providers who design, build, and service their equipment can deliver rapid retrofits (e.g., auto-flushing kits) and closed-loop control logic at lower cost.
  • Sensor data analytics: Machine-learning-based corrosion probes can identify abnormal stagnation by comparing temperature and ORP deltas between flowing and slow-flow points.

10. Design Upgrades to Make Dead Legs Disappear

  1. Loop-Through Layouts: Instead of isolating heat exchangers, adopt a ring-header architecture so flow never stops.
  2. Double Block-and-Bleed Valves: Keep a small bleed through the idle leg without compromising isolation.
  3. Automated Flush Skids: Compact, PLC-controlled skids open solenoid valves based on a timer or ΔP signal—ideal for Bayesian equalization line and expansion stubs.
  4. Quick-Connect Chlorine Dioxide Injection Ports: Enable rapid disinfection on standby equipment before startup.
  5. Elevated Header Placement: Minimize low-point drop legs that invite sludge accumulation.

11. The Bottom Line for Facility Managers

Ignoring dead legs in cooling towers is no longer an option. From Legionella lawsuits to hidden corrosion blowouts, the financial risk dwarfs the modest investment in smart flushing, cross-connections, and design corrections.

By proactively addressing the seven dead legs outlined above—kept piping extensions, Bayesian equalization lines, standby pump headers, idle chiller loops, seasonal economizers, piping drop legs, and dormant sand filters—you protect uptime, compliance, and water-treatment ROI.

Remember: “If water can’t flow, microbes will grow.” Make dead leg management an integral part of your water-treatment program today.

Speak with our Water Treatment Experts today.

CONTACT US

Chemstar Water logo with a green circular, sunburst-like graphic to the left of the white text Chemstar and smaller gray text WATER beneath it, all on a black background.
Three logos: TÜV SÜD ISO 9001 certification badge, a yellow Top Workplaces 2022 banner, and a blue Baltimore Sun Media logo on a black background.
White logos on a black background: “SBA U.S. Small Business Administration,” “SWaM,” and “GSA,” each in bold text, with the A in GSA stylized as a star.

Contact

(800) 364-7177  |  (410) 391-7516

Baltimore, MD 21220

© 2025 International Chemstar Incorporated. All Rights Reserved. Chemstar Water is a trademark registered in the U.S. Patent and Trademark Office in 2021.
  • Link to LinkedIn
Link to: West Texas Has More Water Than You Think—And It Could Power the Next Boom! Data Center : West Texas Link to: West Texas Has More Water Than You Think—And It Could Power the Next Boom! Data Center : West Texas West Texas Has More Water Than You Think—And It Could Power the Next Boom!... Data-Center-West-Texas- The Texas State Capitol dome with a waving Texas flag and a blue sky highlights Chemstar Water, underscoring its vital role in supporting West Texas data center water solutions. The Chemstar Water logo is superimposed in the center of the image. Link to: Closed Cooling Water System Guide Link to: Closed Cooling Water System Guide Diagram of an industrial closed loop cooling system showing a closed chilled water loop circulating through a heat exchanger. Labeled cooling water supply, return, makeup water, and process equipment are included, with arrows indicating flow directions.Closed Cooling Water System Guide
Scroll to top Scroll to top Scroll to top